Seismic resistant electric contact bimetallic thermometer

1、 Main features:

On site temperature display, intuitive and convenient; Safe and reliable, with a long service life;

2. Multiple structural forms that can meet different requirements.

3. The protective pipe material is 1Gr18Ni9Ti stainless steel and molybdenum titanium, with strong pressure resistance and anti-corrosion ability.

MESSAGE

1、 Main features:

On site temperature display, intuitive and convenient; Safe and reliable, with a long service life;

2. Multiple structural forms that can meet different requirements.

3. The protective pipe material is 1Gr18Ni9Ti stainless steel and molybdenum titanium, with strong pressure resistance and anti-corrosion ability.

4. The core pulling thermometer can be maintained or replaced for a short period of time without stopping the machine.

5. The integrated type includes axial, radial, 135 º, universal and other varieties, which are suitable for various on-site installation needs.

2、 Working principle:

The seismic resistant electric contact bimetallic thermometer is composed of bimetallic sheets wound in a circular bending shape. When one end expands due to heat, it drives the pointer to rotate, and the working instrument displays the corresponding temperature value, while preventing environmental vibration. The bimetallic thermometer is filled with silicone oil or separated from the measuring part to achieve shock resistance. Seismic resistant bimetallic thermometers are divided into two types: integrated seismic resistant electric contact bimetallic thermometers and separated seismic resistant electric contact bimetallic thermometers.

3、 Technical parameters:

1. Execution standards: JB/T8803-1998  GB3836-83;

2. nominal diameter of dial: 60mm, 100, 150;

3. Accuracy level: 1.5 level;

4. Thermal response time: ≤ 40S;

5. Protection level: IP55;

6. Angle adjustment error: The angle adjustment error should not exceed 1.0% of its range;